author: 2020-07-01
Switch on the power, the combustion machine starts, and an electric spark is generated between the ignition electrodes. After about 13 seconds of pre-blowing, the oil pump electromagnetic valve opens automatically, and the oil mist from the nozzle is broken by the electric spark and ignited to form a flame.At this point, the flame detector senses the brightness of the flame and the controller is locked.Ignition electrode delay ignition about 15 seconds to stop the ignition, the burner into normal working state.If the ignition is not successful, the flame does not form, or the flame detector does not feel the flame brightness, then after about 10 seconds of safety time, the safety alarm system will act, the starting work program of the burner will be cut off, and the fault red light will be on.At the beginning of the combustion machine, if the flame detector has felt the brightness, the safety system action, the controller does not enter the normal procedure, the solenoid valve will not open, the nozzle does not spray oil, after about 10 minutes of safety time, the fault red light on.Therefore, when starting the burner in the bright place must first cover the flame detector, do not let it see the light, wait for the burner after the flame, immediately let go of the flame detector, otherwise the burner can not work normally.The burner can be restarted after the red light is on for 3 minutes [1].