Common faults and solutions of burners for gas boilers(1)

author: 2020-05-22

Common faults and solutions of burners in gas boilerAIoBoiler Burner

 AIoBoiler Burner

The fault phenomenonAIoBoiler Burner

 AIoBoiler Burner

The cause of the problemAIoBoiler Burner

 AIoBoiler Burner

Ruled out measuresAIoBoiler Burner

 AIoBoiler Burner

1, switch on the power, press start, motor does not turnAIoBoiler Burner

 AIoBoiler Burner

(1) insufficient air pressure lockAIoBoiler Burner

 AIoBoiler Burner

(2) solenoid valve is not strict, joint leakage, check the lockAIoBoiler Burner

 AIoBoiler Burner

(3) open circuit of thermal relayAIoBoiler Burner

 AIoBoiler Burner

(4) at least one condition circuit is not valid (water level, pressure, temperature and whether the program controller is energized and started)AIoBoiler Burner

 AIoBoiler Burner

(1) adjust the air pressure to the specified valueAIoBoiler Burner

 AIoBoiler Burner

(2) clean or repair the solenoid valve pipe jointAIoBoiler Burner

 AIoBoiler Burner

(3) check whether the component is damaged and the motor current according to resetAIoBoiler Burner

 AIoBoiler Burner

(4) check whether the water level, pressure and temperature exceed the limitAIoBoiler Burner

 AIoBoiler Burner

2. After starting, the front purge is normal, but the ignition cannot be startedAIoBoiler Burner

 AIoBoiler Burner

(1) insufficient electric fire air capacityAIoBoiler Burner

 AIoBoiler Burner

(2) electromagnetic valve does not work (main valve, ignition valve)AIoBoiler Burner

 AIoBoiler Burner

(3) solenoid valve burns outAIoBoiler Burner

 AIoBoiler Burner

(4) unstable pressureAIoBoiler Burner

 AIoBoiler Burner

(5) too much airAIoBoiler Burner

 AIoBoiler Burner

(1) check the line and repair itAIoBoiler Burner

 AIoBoiler Burner

(2)AIoBoiler Burner

 AIoBoiler Burner

(3) adjust the air pressure to the specified valueAIoBoiler Burner

 AIoBoiler Burner

(4) reduce the air distribution, reduce the air door openingAIoBoiler Burner

 AIoBoiler Burner

3, the point is not on fire, normal pressure, electricity is not to fireAIoBoiler Burner

 AIoBoiler Burner

(1) the ignition transformer is burnt outAIoBoiler Burner

 AIoBoiler Burner

(2) damage or loss of high voltage wireAIoBoiler Burner

 AIoBoiler Burner

(3) the gap is too large or too small, the relative size of the ignition rod positionAIoBoiler Burner

 AIoBoiler Burner

(4) electrode rupture or short circuit with groundAIoBoiler Burner

 AIoBoiler Burner

(5) improper spacingAIoBoiler Burner

 AIoBoiler Burner

(1)AIoBoiler Burner

 AIoBoiler Burner

(2) reinstall or replaceAIoBoiler Burner

 AIoBoiler Burner

(3) readjustmentAIoBoiler Burner

 AIoBoiler Burner

(4) reinstall or replaceAIoBoiler Burner

 AIoBoiler Burner

(5) readjustmentAIoBoiler Burner

 AIoBoiler Burner

5. After ignition, the fire will be extinguishedAIoBoiler Burner

 AIoBoiler Burner

(1) pressure is insufficient, pressure drop is too large, and the air supply flow is too smallAIoBoiler Burner

 AIoBoiler Burner

(2) the air volume is too small, the combustion is not sufficient, the smoke is thickerAIoBoiler Burner

 AIoBoiler Burner

(3) too much air, white airAIoBoiler Burner

 AIoBoiler Burner

(1) readjust the air pressure and clean the filterAIoBoiler Burner

 AIoBoiler Burner

(2) readjustmentAIoBoiler Burner

 AIoBoiler Burner

(30) readjustmentAIoBoiler Burner

 AIoBoiler Burner

5. White smokeAIoBoiler Burner

 AIoBoiler Burner

(1) the air volume is too smallAIoBoiler Burner

 AIoBoiler Burner

(2) too much humidity in the airAIoBoiler Burner

 AIoBoiler Burner

(3) the exhaust temperature is lowAIoBoiler Burner

 AIoBoiler Burner

(1) turn down the damperAIoBoiler Burner

 AIoBoiler Burner

(2) appropriately reduce air volume and increase air inlet temperatureAIoBoiler Burner

 AIoBoiler Burner

(3) take measures to raise the temperature of smoke exhaustAIoBoiler Burner

 AIoBoiler Burner

The chimney drips waterAIoBoiler Burner

 AIoBoiler Burner

(1) the ambient temperature is lowAIoBoiler Burner

 AIoBoiler Burner

(2) more small fire combustion processAIoBoiler Burner

 AIoBoiler Burner

(3) gas has high hydrogen content and high oxygen content to produce waterAIoBoiler Burner

 AIoBoiler Burner

(4) the chimney is longerAIoBoiler Burner

 AIoBoiler Burner

(5) the exhaust temperature is lowAIoBoiler Burner

 AIoBoiler Burner

(1) reduce air distributionAIoBoiler Burner

 AIoBoiler Burner

(2) reduce the chimney heightAIoBoiler Burner

 AIoBoiler Burner

(3) raise the furnace temperatureAIoBoiler Burner

 AIoBoiler Burner

The throttle stops under controlAIoBoiler Burner

 AIoBoiler Burner

The throttle position switch signal is not fed back to the program signalAIoBoiler Burner

 AIoBoiler Burner

Check whether the damper wiring is loose or whether the switch is out of orderAIoBoiler Burner

 AIoBoiler Burner

Gas boiler burnerAIoBoiler Burner

 AIoBoiler Burner

The fault phenomenonAIoBoiler Burner

 AIoBoiler Burner

The cause of the problemAIoBoiler Burner

 AIoBoiler Burner

Ruled out measuresAIoBoiler Burner

 AIoBoiler Burner

General failureAIoBoiler Burner

 AIoBoiler Burner

7. The burner motor does not workAIoBoiler Burner

 AIoBoiler Burner

(1) no voltageAIoBoiler Burner

 AIoBoiler Burner

(2) the fuse is damagedAIoBoiler Burner

 AIoBoiler Burner

(3) motor failureAIoBoiler Burner

 AIoBoiler Burner

(4) control circuit interruptionAIoBoiler Burner

 AIoBoiler Burner

(5) interruption of gas transmissionAIoBoiler Burner

 AIoBoiler Burner

(6) control failureAIoBoiler Burner

 AIoBoiler Burner

(7) the contactor does not operateAIoBoiler Burner

 AIoBoiler Burner

(8) thermal relay is damagedAIoBoiler Burner

 AIoBoiler Burner

(1) connect the circuitAIoBoiler Burner

 AIoBoiler Burner

(2) replacementAIoBoiler Burner

 AIoBoiler Burner

(3) repairAIoBoiler Burner

 AIoBoiler Burner

(4) find the disconnect point, contact or disconnect the regulator or monitorAIoBoiler Burner

 AIoBoiler Burner

(5) open the ball valve and inform the gas regulatory authority in case of insufficient gas quantity for a long timeAIoBoiler Burner

 AIoBoiler Burner

(6) replacementAIoBoiler Burner

 AIoBoiler Burner

(7) manual reset testAIoBoiler Burner

 AIoBoiler Burner

(8) replace the thermal relayAIoBoiler Burner

 AIoBoiler Burner

Air shortageAIoBoiler Burner

 AIoBoiler Burner

8. The burner motor runs, but stops after prepurgeAIoBoiler Burner

 AIoBoiler Burner

The burner motor runs, but stops after about 20 seconds (for equipment with seal inspection device only)AIoBoiler Burner

 AIoBoiler Burner

(1) air pressure switch is out of orderAIoBoiler Burner

 AIoBoiler Burner

(2) the pressure switch is contaminated and the pipeline is blockedAIoBoiler Burner

 AIoBoiler Burner

(3) the solenoid valve is not sealedAIoBoiler Burner

 AIoBoiler Burner

(1) changeAIoBoiler Burner

 AIoBoiler Burner

(2) cleanAIoBoiler Burner

 AIoBoiler Burner

(3) exclude the case of non-sealingAIoBoiler Burner

 AIoBoiler Burner

9. The burner motor runs, but stops in the pre-purge state after 10 secondsAIoBoiler Burner

 AIoBoiler Burner

(1) pressure switch contact is not connected to the operating position (air pressure is too low)AIoBoiler Burner

 AIoBoiler Burner

(2) the blower is contaminated, and the heat continuesAIoBoiler Burner

 AIoBoiler Burner

(3) the rotation direction of the burner motor is wrongAIoBoiler Burner

 AIoBoiler Burner

(1) adjust the pressure switch correctly and replace it if necessaryAIoBoiler Burner

 AIoBoiler Burner

(2) cleanAIoBoiler Burner

 AIoBoiler Burner

(3) power pole changeAIoBoiler Burner

 AIoBoiler Burner

Ignition failureAIoBoiler Burner

 AIoBoiler Burner

10. The burner motor runs, and the voltage is applied to the terminal post 16 of the controller. There is no ignitionAIoBoiler Burner

 AIoBoiler Burner

(1) the ignition electrode distance is too largeAIoBoiler Burner

 AIoBoiler Burner

(2) being pollutedAIoBoiler Burner

 AIoBoiler Burner

(3) grounding the ignition electrode or circuitAIoBoiler Burner

 AIoBoiler Burner

(4) ignition transformer failsAIoBoiler Burner

 AIoBoiler Burner

(1) adjust the electrode spacingAIoBoiler Burner

 AIoBoiler Burner

(2) cleaningAIoBoiler Burner

 AIoBoiler Burner

(3) remove grounding and replace damaged electrodes or cablesAIoBoiler Burner

 AIoBoiler Burner

(4) replace ignition transformerAIoBoiler Burner

 AIoBoiler Burner

Flame formationAIoBoiler Burner

 AIoBoiler Burner

11. The motor is running and ignition is normal, but it stops after failureAIoBoiler Burner

 AIoBoiler Burner

(1) the solenoid valve is not open because of coil damage or cable breakAIoBoiler Burner

 AIoBoiler Burner

(1) replace the solenoid valve or troubleshoot the circuit failure, check the voltage at terminal 17AIoBoiler Burner

 AIoBoiler Burner

12. In the equipment with sealing inspection device, the sealing is not strict;Burner motor running, ignition normal, but later stop (no fault display)AIoBoiler Burner

 AIoBoiler Burner

(1) the solenoid valve is not sealedAIoBoiler Burner

 AIoBoiler Burner

(2) insufficient air supplyAIoBoiler Burner

 AIoBoiler Burner

(3) the filter is blockedAIoBoiler Burner

 AIoBoiler Burner

(1) exclude the case of not sealingAIoBoiler Burner

 AIoBoiler Burner

(2) cleaning or replacementAIoBoiler Burner

 AIoBoiler Burner

Common faults of gas boiler burners and their solutions iiAIoBoiler Burner

 AIoBoiler Burner

The fault phenomenonAIoBoiler Burner

 AIoBoiler Burner

The cause of the problemAIoBoiler Burner

 AIoBoiler Burner

Elimination methodAIoBoiler Burner

 AIoBoiler Burner

Shut down after flame formationAIoBoiler Burner

 AIoBoiler Burner

13. Flame formation, but shutdown under rated load operationAIoBoiler Burner

 AIoBoiler Burner

(1) contamination of the filterAIoBoiler Burner

 AIoBoiler Burner

(2) pressure regulating valve because of inertia workAIoBoiler Burner

 AIoBoiler Burner

(3) gas meter failure or water accumulation in deep pipeAIoBoiler Burner

 AIoBoiler Burner

(1) clean the filterAIoBoiler Burner

 AIoBoiler Burner

(2) check the oil suction nozzleAIoBoiler Burner

 AIoBoiler Burner

(3) inform the gas regulatory agencyAIoBoiler Burner

 AIoBoiler Burner

Flame monitoring failure during power generationAIoBoiler Burner

 AIoBoiler Burner

14. The burner motor runs, the ignition can be heard, the flame is formed normally, but then the fault stopsAIoBoiler Burner

 AIoBoiler Burner

(1) the ionization current is unstable and too lowAIoBoiler Burner

 AIoBoiler Burner

(2) uneven mixing regulation of gas and airAIoBoiler Burner

 AIoBoiler Burner

(3) the ignition spark affects the ionization currentAIoBoiler Burner

 AIoBoiler Burner

(1) change the ionization electrode position;Remove excessive environmental resistance from ionizing circuits and terminals (tighten terminals)AIoBoiler Burner

 AIoBoiler Burner

(2) readjustment (re-debugging)AIoBoiler Burner

 AIoBoiler Burner

(3) primary coil replacement phase line and Central Line of ignition transformerAIoBoiler Burner

 AIoBoiler Burner

15. Flame sensorAIoBoiler Burner

 AIoBoiler Burner

(1) contamination of uv probeAIoBoiler Burner

 AIoBoiler Burner

(2) the light is too weakAIoBoiler Burner

 AIoBoiler Burner

(3) the ultraviolet probe is out of orderAIoBoiler Burner

 AIoBoiler Burner

(1) cleaning (grease removal)AIoBoiler Burner

 AIoBoiler Burner

(2) detect the amount of combustion regulating wind and gasAIoBoiler Burner

 AIoBoiler Burner

(3) replacementAIoBoiler Burner

 AIoBoiler Burner

pumpAIoBoiler Burner

 AIoBoiler Burner

16. No oilAIoBoiler Burner

 AIoBoiler Burner

(1) pump failureAIoBoiler Burner

 AIoBoiler Burner

(2) oil transfer pressure power reductionAIoBoiler Burner

 AIoBoiler Burner

(3) the oil inlet valve is not sealedAIoBoiler Burner

 AIoBoiler Burner

(4) the inlet pipe is not sealedAIoBoiler Burner

 AIoBoiler Burner

(5) the stop valve is closedAIoBoiler Burner

 AIoBoiler Burner

(6) contamination of the filterAIoBoiler Burner

 AIoBoiler Burner

(7) the filter is not sealedAIoBoiler Burner

 AIoBoiler Burner

(8) the tubing is not sealedAIoBoiler Burner

 AIoBoiler Burner

(9) pump suction airAIoBoiler Burner

 AIoBoiler Burner

(10) too high vacuum in the tubingAIoBoiler Burner

 AIoBoiler Burner

(1) changeAIoBoiler Burner

 AIoBoiler Burner

(2) the change of pumpAIoBoiler Burner

 AIoBoiler Burner

(3) remove the oil inlet valve to clean or replaceAIoBoiler Burner

 AIoBoiler Burner

(4) seal the inlet pipeAIoBoiler Burner

 AIoBoiler Burner

(5) openAIoBoiler Burner

 AIoBoiler Burner

(6) cleanAIoBoiler Burner

 AIoBoiler Burner

(7) replace the sealing ringAIoBoiler Burner

 AIoBoiler Burner

(8) screw tight and exhaustAIoBoiler Burner

 AIoBoiler Burner

(9) screw tight and exhaustAIoBoiler Burner

 AIoBoiler Burner

(10) clean the filter and valveAIoBoiler Burner

 AIoBoiler Burner

The nozzleAIoBoiler Burner

 AIoBoiler Burner

17. Uneven atomizationAIoBoiler Burner

 AIoBoiler Burner

(1) the nozzle is contaminated or wornAIoBoiler Burner

 AIoBoiler Burner

(1) clean the nozzle or replace itCommon faults and solutions of burners for gas boilersAIoBoiler Burner