  In addition to the installation of the fan in accordance with the relevant standards and in accordance with the design institute drawings requirements for construction.The fan shall be installed in such a place as is necessary for normal operation and easy maintenance.cOoBoiler Burner

  During installation, soft connection is recommended between the fan and the air duct, the length should not be less than 200mm, and the pipe diameter should be the same as the inlet and outlet size of the fan.In order to ensure that the soft connection does not appear distortion in the process of system debugging, the installation should be moderately tight.The pipe diameter of the smoke and air duct at the outlet of the fan can only be enlarged, not reduced.If there is a guide plate for soft connection, please pay attention to the direction of airflow.cOoBoiler Burner

  A soft connection is also suggested between the inlet and outlet of the burner, and the air duct between the blower and the burner should maintain a certain Angle.Not suitable for vertical layout, vertical layout is easy to cause uneven combustion, vibration.Fan into the tuyere are generally adjustable door, the installation of inlet damper should pay attention to whether the direction of guide flow formed by the blade Angle when opened is consistent with the impeller rotation direction.cOoBoiler Burner